● Active grounding system for static grounding and permanent monitoring
● Permanent removal of electrostatic charge during filling or emptying tanks (road tracks, railcar tanks, barrels)
● Two output contacts
Product information "TEPEX GGCD Explosion Proof Grounding Control"
TEPEX GGCD Explosion Proof grounding control device
CONSTRUCTION
Enclosure: polyester plastic reinforced with glass fiber, color – black Cover: with integrated Thermoplastic elastomer gasket, closes with four M6 stainless steel screws.
Apparatus category:
II 2GD
Explosion protection:
Ex d e [ib] mb IIC T5 Gb
Enviroment temperature:
-20ºC ≤ Ta ≤ +50ºC [ATEX]
-50ºC ≤ Ta ≤ +50ºC [EAC]
Degree of protection:
IP66
Rated insulation voltage:
230V
Specification
Certificate:
FIDI 19 ATEX 0050, EAC RU C-HR.AB24.B.03293
Marking:
CE0722
Apparatus category:
II 2GD
Marking of explosion protection:
Ex eb db [ib] mb IIC T5 Gb
Ex tb IIIC T80° Db
Ambient temperature:
-20ºC ≤ Ta ≤ +50ºC -50ºC ≤ Ta ≤ +50ºC
Degree of protection:
IP 66 category 1
Resistance to shock:
IK 08
Protection class :
I (protective earthing)
Rated voltage:
230 V± 10%
Rated current:
50 mA
Frequency:
50Hz
Output circuit:
2 NO/NC Un=250VAC, In=8A / 230V, 4A at cosj=0.4
Cable entry:
3 x M25 – power supply, two output circuit 4 x M25 – 2x connection clamp , 2x wire to equipotential busbar or grounding
Weight:
6 kg (without clamp and cable) weight of clamps with 10 m cable ca. 2,5 kg